SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 13 and November 22, 2023, SCI initially collected 38 drinking water samples (BBES-1 through BBES-38) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 6 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. These fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on December 14, 2023, 12 drinking water samples were collected from fixtures which previously exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this sampling event, one sample location exceeded the AL. Further remediation activities were recommended for this fixture.

During SCI’s resampling event on November 27, 2024, 1 drinking water was collected from the fixture which previously exceeded the AL. During this sampling event, the location was below the AL and was returned to service.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

All drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, below. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

Sample Number Sample Location Sample Description Initial Result (ppb) Resampling - First Draw (ppb) Resampling - Second Draw (ppb) Second Resampling (ppb)
BBES-8 Kitchen Double Sink Round Sink 360 9.6 <1.0 2.93
BBES-8SVH 42.4 NS
BBES-8SVC 25.8 NS
BBES-9 Kitchen Double Sink Left Sink 25.3 1.5
BBES-12 Kitchen Triple Basin Left Sink 8.97 4.2 <1.0 NS
BBES-13 Kitchen Triple Basin Right Sink 11.6 4.7 1.2 NS
BBES-14 Kitchen Handwash Sink 12.3 2.7 <1.0 NS
BBES-17 Kitchen Combi-Oven 14.9 <1.0 <1.0 NS

NS – Not Sampled

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.