Testing Results
Blevins Elementary
SCI collected 36 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | 2nd Retest Result | Returned to Service |
|---|---|---|---|---|---|---|---|---|
| Kitchen | Food Line Sink | 8.71 | Replaced fixture |
33.9 |
1.3 | cleaned aerator | 2.93 | |
| Kitchen | Food Prep Right Sink | 15.1 | Replaced fixture | 20 | 1.3 | cleaned aerator | 2.67 | |
| Kitchen | Left Faucet Triple Basin Sink | 13.9 | Replaced fixture | 79.8 | 6.3 | cleaned aerator | 35 | |
| Kitchen | Center Faucet Triple Basin Sink | 22.5 | Replaced fixture | 42.8 | 23.3 | cleaned aerator | 14.4 | |
| Kitchen | Right Faucet Triple Basin Sink | 32.3 | Replaced fixture | 47.1 | 12 | cleaned aerator | 21.8 | |
| Room 3 | Water Fountain Attached to Sink | 8.18 | Removed fixture |