Testing Results

Center for Creative Learning
Updated

SCI collected 30 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Return to Service
Nurse's Office Sink 63.3 replaced aerator 3.7 <1.0     1/5/2024
Nurse's Office Bathroom Sink 9.19 replaced aerator 1.8 <1.0     1/5/2024
Room 1 Water Fountain Attached to Sink 12.1 eliminate fixture         N/A
Room 3 Water Fountain Attached to Sink 17.1 eliminate fixture         N/A
Room 4 Water Fountain Attached to Sink 10.7 eliminate fixture         N/A
Kitchen East Handwash Sink 6.88 replaced aerator 3.3 <1.0     12/4/2023
Kitchen Double Basin Sink 9.46 replaced aerator <1.0 <1.0     12/4/2023
Kitchen Southwest Handwash Sink 6.91 replaced aerator 6.2 <1.0 fixture to be replaced by contractor   9/20/24
Room 10 Water Fountain Attached to Sink 11.7 eliminate fixture         N/A
Room 11 Water Fountain Attached to Sink 8.31 eliminate fixture         N/A