Center for Creative Learning
SCI collected 30 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | Retest Result | Return to Service |
|---|---|---|---|---|---|---|---|---|
| Nurse's Office | Sink | 63.3 | replaced aerator | 3.7 | <1.0 | 1/5/2024 | ||
| Nurse's Office Bathroom | Sink | 9.19 | replaced aerator | 1.8 | <1.0 | 1/5/2024 | ||
| Room 1 | Water Fountain Attached to Sink | 12.1 | eliminate fixture | N/A | ||||
| Room 3 | Water Fountain Attached to Sink | 17.1 | eliminate fixture | N/A | ||||
| Room 4 | Water Fountain Attached to Sink | 10.7 | eliminate fixture | N/A | ||||
| Kitchen | East Handwash Sink | 6.88 | replaced aerator | 3.3 | <1.0 | 12/4/2023 | ||
| Kitchen | Double Basin Sink | 9.46 | replaced aerator | <1.0 | <1.0 | 12/4/2023 | ||
| Kitchen | Southwest Handwash Sink | 6.91 | replaced aerator | 6.2 | <1.0 | fixture to be replaced by contractor | 9/20/24 | |
| Room 10 | Water Fountain Attached to Sink | 11.7 | eliminate fixture | N/A | ||||
| Room 11 | Water Fountain Attached to Sink | 8.31 | eliminate fixture | N/A |