Skip To Main Content

Logo Image

Logo Title

Rockwood School District
We do whatever it takes to ensure all students realize their potential.

Testing Results

Center for Creative Learning

Posted

SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 25, 2023, SCI initially collected 30 drinking water samples (CCL-1 through CCL-30) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 10 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. Five of the fixtures were removed from use. The remaining 5 fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on November 17 and December 12, 2023, 10 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resampling event, 4 of the fixtures were under the AL and were returned to service. The remaining fixture was still above the AL, and further remediation activities were recommended.

During SCI’s resampling event on November 27, 2024, 1 drinking water sample was collected from the final fixture which had previously exceeded the AL. During this resampling event, the fixture was still above the AL. Following this resampling event, the fixture was removed from use.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratoryprovided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, below. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

Sample Number Sample Location Sample Description Initial Result (ppb) Resampling - First Draw (ppb) Resampling - Second Draw (ppb) 2nd Resample (ppb)
CCL-1 Nurse's Office Sink 63.3 3.7 <1.0 NS
CCL-2 Nurse's Office Bathroom Sink 9.19 1.8 <1.0 NS
CCL-7 Room 1 Water Fountain Attached to Sink 12.1 NS (removed)
CCL-8 Room 3 Water Fountain Attached to Sink 17.1 NS (removed)
CCL-9 Room 4 Water Fountain Attached to Sink 10.7 NS (removed)
CCL-12 Kitchen East Handwash Sink 6.88 3.3 <1.0 NS
CCL-18 Kitchen Double Basin Sink 9.46 <1.0 <1.0 NS
CCL-19 Kitchen Southwest Handwash Sink 6.91 6.2 <1.0 15.7 (removed)
CCL-22 Room 10 Water Fountain Attached to Sink 11.7 NS (removed)
CCL-30 Room 11 Water Fountain Attached to Sink 8.31 NS (removed)

NS – Not Sampled

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb, or the fixture were removed from service. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.

Download the Report (PDF)