Testing Results

Chesterfield Elementary
Updated

SCI collected 36 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Return to Service
Kitchen Food Prep Sink 8.4 replaced aerator 4.7 <1.0     11/29/2023
Kitchen North Handwash Sink 6.04 replaced aerator 3.2 <1.0     11/29/2023
Kitchen Three Basin Sink Left Sink 57.1 replaced aerator 18.1 <1.0 fixture replaced 2.18 09/23/2024
Kitchen Three Basin Sink Right Sink 6.44 replaced aerator 2.2 <1.0     11/29/2023
Kitchen South Handwash Station 10.3 replaced aerator 5.1 <1.0 fixture replaced 1.54 09/20/24
Hallway Outside Room 5 Bottle Filler 26.7 replaced fixture <1.0 <1.0     06/17/2024
Room 8 Drinking Fountain 8.94 removed fixture          