SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 11, 2023, SCI initially collected 36 drinking water samples (CES-1 though CES-36) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 7 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. One fixture was removed, the other six were taken out of service until remediation activities could be completed.

During SCI’s resampling event on November 17, 2023, 10 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw samples were collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resampling event, 3 fixtures were below the AL and were returned to service, the remaining 2 fixtures were above the AL, and further remediation activities were recommended.

During SCI’s resampling event on May 10, 2024, 1 drinking water sample was collected from a fixture which previously exceeded the AL. During this resampling event, the fixture was below the AL and was returned to service.

During SCI’s resampling event on June 10, 2024, 2 drinking water samples were collected from fixtures which previously exceeded the AL. During this resampling event, both fixtures were below the AL and were returned to service.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratoryprovided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, below. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

Sample Number Sample Location Sample Description Initial Result (ppb) Resampling - First Draw (ppb) Resampling - Second Draw (ppb) 2nd Resample (ppb)
CES-4 Kitchen Food Prep Sink 8.4 4.7 <1.0 NS
CES-5 Kitchen North Handwash Sink 6.04 3.2 <1.0 NS
CES-6 Kitchen Three Sink Basin Left Sink 57.1 18.1 <1.0 2.18
CES-8 Kitchen Three Sink Basin Right Sink 6.44 2.2 <1.0 NS
CES-9 Kitchen South Handwash Station 10.3 5.1 <1.0 1.54
CES-17 Hallway Outside Room 5 Bottle Filler 26.7 NS <1.0
CES-24 Room 8 Drinking Fountain 8.94 NS

NS – Not Sampled