Testing Results

Crestview Middle

Posted

SCI collected 61 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Return to Service
Snack Bar Food Line Faucet 14.1 replaced aerator 11.8 <1.0   15.7  
Snack Bar Food Line Faucet 9.18 replaced aerator 10.8 <1.0   20.1  
Kitchen Food Prep Sink 365 replaced aerator 1.2 <1.0     1/19/2024

Download the Report (PDF)