Testing Results

Crestview Middle

Posted

SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 25 and 26, and August 16 and 17, 2023, SCI initially collected 61 drinking water samples (CMS-01 through CMS-62) from various water fixtures located throughout the structure and submitted them for analytical testing. A sample number was inadvertently skipped in the field resulting in sample identification up to CMS-62. During this sampling event, 6 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. These fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on December 13, 2023, 12 drinking water samples were collected from fixtures which exceeded the AL. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw samples were collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resampling event, 4 samples locations exceeded the AL. Two of these fixtures were designated as “not for drinking water,” further remediation activities were recommended on the other two.

During SCI’s resampling events on November 29, 2024, and July 7, 2025, the two samples locations that had previously exceeded the AL were retested. During both of these sampling events, the locations were still above the AL, and further remediation activities were recommended.

On March 20, 2026, SCI remobilized to the site to sample the two fixtures which had previously exceeded the AL. During this sampling event, both locations were below the AL and were returned to service. All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. -SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures. Figures depicting the locations of the sampled water fixtures are enclosed. The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an AL of 5 parts per billion (ppb).

The drinking water samples which initially exceeded the AL are identified in Table 1, attached. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.

Download the Report (PDF)