Testing Results

Early Childhood - Eureka

Posted

SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 18, 2023, SCI initially collected 14 drinking water samples (EECC-1 though EECC-14) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 9 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. One fixture was made into a “non-potable” water source, the remaining fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on December 14, 2023, 10 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resample event, 1 fixture was below the AL and was returned to service. The remaining fixtures were above the AL, and further remediation activities were recommended.

During SCI’s resampling event on January 12, 2024, 8 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resample event, all four fixtures were above the AL. As such, three of the fixtures were removed from use, and the fourth was made into a “non-potable” water source.

During the resampling event on November 27, 2024, three fixtures were tested which had previously exceeded the AL. During this retesting event, 2 fixtures were below the AL and were returned to service.

The third fixture was above the AL, and further remediation activities were recommended. During the resampling event on July 7, 2025, the remaining fixture that had previously exceeded the AL was retested. During this resampling event, the fixture was below the AL and was returned to service.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, below. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

Sample Number Sample Location Sample Description Initial Result (ppb) Resample 1st Draw Resample 2nd Draw 2nd Resample 1st Draw 2nd Resample 2nd Draw 3rd Resample 4th Resample
7/18/23 12/14/23 1/12/24 11/27/24 7/7/25
EECC-04 Staff Lounge Sink 5.65 <1.0 <1.0 NS NS NS NS
EECC-05 Hallway Outside Conference Room Water Fountain 7.09 NS NS NS NS 4.06 NS
EECC-06 Hallway Outside Conference Room Bottle Filler 6.34 NS NS NS NS 8.84 2.99
EECC-09 Kitchen Three Basin Sink, Left Sink 30.4 111 18.3 14.7 7.5 [1] - -
EECC-10 Kitchen Three Basin Sink, Right Sink 60.1 62.1 571 3.4 8.2 [1] - -
EECC-11 Kitchen Handwash Sink 37.5 50.1 5.1 59.3 1.1 [1] - -
EECC-12 Nurse's Office Sink 6.05 8.3 <1.0 7.1 [2] - - -
EECC-13 Nurse's Office Fridge Ice Machine 29.7 [2] - - - - - -
EECC-14 Hallway Outside 2nd Floor Bathroom Water Fountain 7.04 NS NS NS NS 1.39 NS

NS – Not Sampled
[1] Fixture removed from service
[2] Fixture labeled for non-potable use only

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.

Download the Report (PDF)