Testing Results

Early Childhood - Vandover

Posted

SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 14, 2023, SCI initially collected 12 drinking water samples (VECC-1 through VECC-12) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 1 sample location exceeded the action level (AL) of 5.0 micrograms lead per liter of water. This fixture was taken out of service until remediation activates could be completed.

During SCI’s resampling, two drinking water samples were collected from the fixture which exceeded 5.0 micrograms lead per liter of water. In addition to the first draw sample, SCI also collected a second draw sample during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this sampling event, the fixture still exceeded the AL, and further remediation activates were recommended.

During SCI’s resampling events on November 27, 2024 and July 7, 2025, the previous fixture which exceeded the AL was retested. During the resampling event, the fixture was still above the AL, and further remediation activities were recommended.

During SCI’s resampling event on March 20, 2026, the fixture which had previously exceeded the AL was retested. During this resampling event, the fixture was below the AL and was returned to service. All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, attached. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.