Skip To Main Content

Logo Image

Rockwood School District

Logo Title

Testing Results

Eureka High
Updated

SCI collected 137 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Return to Service
Room D116 Sink 3 - Right Faucet 11.9 replaced aerator 1.0 <1.0     12/4/2023
Room D116 Sink 5 - Left Faucet 5.4 replaced aerator 1.5 <1.0     12/4/2023
Room D116 Sink 5 - Right Faucet 7.26 replaced aerator <1.0 <1.0     12/4/2023
Room D116 Sink 4 - Left Faucet 8.72 replaced aerator <1.0 <1.0     12/4/2023
Room D116 Sink 4 - Right Faucet 14.3 replaced aerator <1.0 <1.0     12/4/2023
Kitchen North Handwash Sink 17.6 replaced aerator 14.7 1.3 fixture replaced   09/20/24 (handwash only)
Kitchen Food Line Faucet 8.47 replaced aerator 9.9 9.8 fixture replaced <1.0 07/29/24
Kitchen Kettle Faucet 173 replaced aerator 111 27.1 fixture replaced 4.81

6/14/2024

Kitchen Wall Faucet 183 replaced aerator 101 1.8 fixture replaced 2.07 6/14/2024
Kitchen Southwest Food Line Faucet 66.4 replaced aerator <1.0 20.8 fixture replaced    
Kitchen Southwest Central Food Line Faucet 52.4 replaced aerator 32.9 19.8 fixture replaced    
Kitchen Northeast Central Food Line Faucet 65.0 replaced aerator 34.7 4.9 fixture replaced    
Kitchen Southwest Handwash Sink 7.14 replaced aerator 33.4 5.5 fixture replaced 26.1 9/20/2024 (handwash only)
Kitchen Sink (to the right of Southwest Handwash Sink) 13.1 replaced aerator 19.7 5.3 fixture replaced 3.82  
Hallway Outside Bathroom near Room E124 Right Fountain 7.51 fixture replaced

2.14

2.14     6/14/2024
Hallway Outside Bathroom near Room E124 Right Bottle Filler 5.89 fixture replaced 3.98 3.98     6/14/2024
Hallway Outside Bathroom near Room E124 Left Fountain 5.61 fixture replaced 2.85 2.85     6/14/2024
Hallway Outside Bathroom near Room E124 Left Bottle Filler 5.25 fixture replaced 5.51 5.51      
Pool Water Fountain 48.3 fixture replaced   <1.0     6/14/2024
Pool Bottle Filler 14.3 fixture replaced   <1.0     6/14/2024
Hallway by Gym B Water Fountain 6.58 fixture replaced   6.18   2.55  
Room F124 Bottle Filler 7.27 fixture replaced   2.64     6/14/2024
Hallway by Room F133 Water Fountain 9.99 fixture replaced   10.5   6.95  
Hallway by Room C128 Water Fountain 40.4 fixture replaced   1.17     6/14/2024
Hallway by Main Entrance East Water Fountain 7.85 fixture replaced   4.64     6/14/2024
Room E133 Sink 5.2 replaced aerator 12.5 1.5 fixture replaced   marked hand wash only

Download the Report (PDF)

All Results