Testing Results

Eureka High

Posted

SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On August 2 and 17, 2023, SCI initially collected 137 drinking water samples (EHS-1 through EHS-137) from various water fixtures located throughout the structure. During this sampling event, 29 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. Following this sampling event, 3 of the fixtures were removed, the remaining 26 fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on November 18 and December 13, 2023, 30 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resample event, 5 of the fixtures were now under the AL and were returned to service. The remaining 10 fixtures were above the AL, and further remediation activities were recommended. Following this resampling event, 2 fixtures were removed.

During SCI’s resampling event on May 22, 2024, 15 fixtures which previously exceeded the AL were resampled. During this resampling event, 11 fixtures were below the AL and were returned to service. The remaining 4 fixtures were above the AL, and further remediation activities were recommended. Following this resampling event, 1 fixture was removed.

During SCI’s resampling event on June 19, 2024, 1 fixtures which previously exceeded the AL was resampled. During this resampling event, the fixture was below the AL and was returned to service.

During SCI’s resampling event on November 27, 2024, 3 fixtures which previously exceeded the AL were resampled. During this resampling event, 2 fixtures were below the AL and were returned to service. The remaining fixture was above the AL, and further remediation activities were recommended.

During SCI’s resampling event on July 7, 2025, 4 fixtures which previously exceeded the AL were resampled. During this resampling event, 3 fixtures were below the AL and were returned to service. The remaining fixture was above the AL, and further remediation activities were recommended.

During SCI’s resampling event on March 20, 2026, 1 fixtures which previously exceeded the AL was resampled. During this resampling event, the fixture was below the AL and was returned to service.

The remaining fixture was above the AL, and further remediation activities were recommended.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, attached. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.