Testing Results

Fairway Elementary
Updated

SCI collected 36 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Return to Service
Kitchen Dish Washroom Middle Sink 8.45 replaced aerator 4.4 <1.0     1/17/2024
Kitchen Dish Washroom Right Sink 8.69 replaced aerator 5.3 <1.0 replaced fixture 31.8  
Kitchen Food Prep Triple Sink Left Sink 10.8 replaced aerator 12.3 4.9      
Kitchen Food Prep Triple Sink Middle Sink 5.78 replaced aerator 3.0 <1.0     1/17/2024
Kitchen Food Steamer 21.7 replaced aerator 5.6 <1.0   2.87  
Teacher's Lounge Water/Ice Machine 6.30 disconnected          

Download the Report (PDF)

All Results