Testing Results
Geggie Elementary
SCI collected 39 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | 2nd Retest Result | 3rd Remediation | 3rd Retest Result | Returned to Service |
|---|---|---|---|---|---|---|---|---|---|---|
| Room 27 | Water Fountain | 80.4 | removed fountain | N/A | ||||||
| Room 25 | Water Fountain | 58.6 | removed fountain | N/A | ||||||
| Kitchen | East Handwash Sink | 6.18 | replaced aerator | 15.9 | 2.4 | replaced fixture | 49.4 | cleaned aerator | ||
| Kitchen Double Basin | Left Sink | 11.2 | replaced aerator | 7.1 | 1.4 | replaced faucet | 15.1 | cleaned aerator | ||
| Kitchen | West Handwash Sink | 7.32 | replaced aerator | <1.0 | <1.0 | 1.17.2024 | ||||
| Kitchen Triple Basin | Left Sink | 6.24 | replaced aerator | 11.8 | <1.0 | replaced faucet | 14.0 | cleaned aerator | 4.22 | |
| Kitchen Triple Basin | Middle Sink | 12.2 | replaced aerator | 16.5 | <1.0 | replaced faucet | 5.5 | cleaned aerator | ||
| Kitchen Triple Basin | Right Sink | 99.4 | replaced aerator | 20.1 | <1.0 | replaced faucet | 11.4 | cleaned aerator | ||
| Kitchen Triple Basin | Faucet | 8.39 | replaced aerator | 4.8 | <1.0 | 1.17.2024 | ||||
| Teacher's Lounge | Fridge Water Dispenser | 6.82 | disconnected |