Testing Results

Geggie Elementary
Updated

SCI collected 39 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation 2nd Retest Result 3rd Remediation 3rd Retest Result Returned to Service
Room 27 Water Fountain 80.4 removed fountain             N/A
Room 25 Water Fountain 58.6 removed fountain             N/A
Kitchen East Handwash Sink 6.18 replaced aerator 15.9 2.4 replaced fixture 49.4 cleaned aerator    
Kitchen Double Basin Left Sink 11.2 replaced aerator 7.1 1.4 replaced faucet 15.1 cleaned aerator    
Kitchen West Handwash Sink 7.32 replaced aerator <1.0 <1.0         1.17.2024
Kitchen Triple Basin Left Sink 6.24 replaced aerator 11.8 <1.0 replaced faucet 14.0 cleaned aerator 4.22  
Kitchen Triple Basin Middle Sink 12.2 replaced aerator 16.5 <1.0 replaced faucet 5.5 cleaned aerator    
Kitchen Triple Basin Right Sink 99.4 replaced aerator 20.1 <1.0 replaced faucet 11.4 cleaned aerator    
Kitchen Triple Basin Faucet 8.39 replaced aerator 4.8 <1.0         1.17.2024
Teacher's Lounge Fridge Water Dispenser 6.82 disconnected              

Download the Report (PDF)