Testing Results
Kehrs Mill Elementary
SCI collected 21 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | Retest Result | Returned to Service |
|---|---|---|---|---|---|---|---|---|
| Kitchen | Food Prep Sink | 6.97 | replaced aerator | <1.0 | <1.0 | 1/19/2024 | ||
| Kitchen Triple Basin | Middle Sink | 6.67 | replaced aerator | 5.5 | <1.0 | replaced fixture | 1.26 | |
| Kitchen Triple Basin | Right Sink | 90.4 | replaced aerator | 14.9 | <1.0 | replaced fixture | 6.09 | |
| Work Room | Sink | 12.1 | replaced aerator | 42.4 | <1.0 | replaced fixture | <1.0 | |
| Nurse's Office | Sink | 5.34 | replaced aerator | <1.0 | <1.0 | 1/03/2024 | ||
| Room 1 | Sink | 6.12 | replaced aerator | <1.0 | <1.0 | 1/23/2024 | ||