SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 11, 2023, SCI initially collected 21 drinking water samples (KMES-1 though KMES-21) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 7 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. These fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on December 13, 2023, 14 drinking water samples were collected from the fixtures that exceeded 5.0 micrograms lead per liter of water. In addition to the first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this resample event, 3 fixtures were below the AL and were returned to service. One fixture was removed from use. The remaining fixtures were above the AL, and further remediation activities were recommended.

During SCI’s resampling event on June 20, 2024, the remaining three fixtures that previously exceeded the AL were retested. During this sampling event, two of the fixtures were under the AL and were returned to service. The remaining fixture was above the AL, and further remediation activities were recommended.

During SCI’s resampling events on November 27, 2024, and July 7, 2025, the remaining fixture which previously exceeded the AL was retested. During both resampling events, the fixture was still above the AL, and further remediation activities were recommended.

During the resampling event on March 20, 2026, the remaining fixture that had previously exceeded the AL was retested. During this resampling event, the fixture was below the AL and was returned to service.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. The drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, enclosed. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.