Kellison Elementary
Updated

SCI collected 24 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Returned to Service
Kitchen Kettle Faucet 20.0 replaced aerator 111 <1.0 fixture to be replaced 7.11  
Kitchen Single Basin Sink 12.4 replaced aerator 1.2 <1.0     11/30/2023
Room 24 Water Fountain 28.4            