Testing Results
Lafayette High
SCI collected 105 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | Retest Result | Returned to Service |
|---|---|---|---|---|---|---|---|---|
| Food Line | Sink | 5.8 | replaced aerator | 2.7 | <1.0 | 11/29/2023 | ||
| Food Line | Frymaster Faucet | 52.9 | replaced aerator | 4.8 | <1.0 | 11/29/2023 | ||
| Kitchen | Kettle Faucet | 9.2 | replaced aerator | 3.0 | <1.0 | 11/29/2023 | ||
| Kitchen | Handwash Sink | 13.6 | replaced aerator | 5.8 | <1.0 | replaced fixture | 1.3 | 05/14/24 |
| Kitchen | Mixer Faucet | 199 | replaced aerator | 199 | 7.2 | replaced fixture | 6.2 | |
| Room 109 | Left Faucet Triple Basin Sink | 14.6 | replaced aerator | 4.6 | <1.0 | 12/8/2023 | ||
| Room 109 | Right Faucet Triple Basin Sink | 8.1 | replaced aerator | 3.2 | <1.0 | 12/15/2023 | ||
| Room 109 | Southern Sink | 191 | replaced aerator | <1.0 | <1.0 | 12/15/2023 |