Testing Results
LaSalle Springs Middle
SCI collected 63 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | Retest Result | Return to Service |
|---|---|---|---|---|---|---|---|---|
| Entrance by Door 2 | Center Fountain | 5.45 | replaced fixture | <1.0 | ||||
| Kitchen Serving Area | Handwash Sink | 5.92 | replaced aerator | 2.3 | <1.0 | 12/11/2023 | ||
| Kitchen Dish Room | Handwash Sink | 5.20 | replaced aerator | 1.7 | <1.0 | 12/14/2023 | ||
| Kitchen Dish Room | Right Faucet Triple Basin Sink | 8.26 | replaced aerator | <1.0 | <1.0 | 12/11/2023 | ||
| Kitchen | Pan Faucet | 45.4 | replaced aerator | 6.5 | <1.0 | replaced fixture | 4.2 | 04/09/24 |
| Kitchen | Handwash Sink | 7.39 | replaced aerator | 1.4 | <1.0 | 12/11/2023 | ||
| Kitchen | Wall Mounted Faucet | 61.4 | replaced aerator | 1.2 | <1.0 | 12/11/2023 |