Testing Results
Marquette High
SCI collected 88 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Result | Retest 2nd Draw Result | 2nd Remediation | Retest Result | Return to Service |
|---|---|---|---|---|---|---|---|---|
| Kitchen Triple Basin | Left Sink | 12.9 | replaced aerator | <1.0 | <1.0 | 12/8/2023 | ||
| Kitchen | Big Steam Kettle Faucet | 38.0 | replaced aerator | 177 | 2.3 | fixture replaced | 4.81 | 8/9/24 |
| Kitchen Kettle Room | Jug Filler | 388 | replaced aerator | 55.1 | 2.2 | fixture replaced | 8.0 | |