Testing Results

Pathways Wellness/Administrative Annex

Posted

SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 18 and 28, 2023, SCI collected 10 drinking water samples (PWC-1 though PWC-10) from various water fixtures located throughout the structures and submitted them for analytical testing. During this sampling event, 4 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. These fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on March 29 and November 27, 2024, drinking water samples were collected from the fixtures which exceeded 5.0 micrograms lead per liter of water. During this resampling event, 3 of the sample fixtures were below the AL and were returned to service. The sample was above the AL, and further remediation activities were recommended.

During SCI’s resampling event on July 7, 2025, the fixture which had previously exceeded the AL was retested. During this resampling event, the fixture still exceeded the AL, and further remediation activities were recommended.

During SCI’s resampling event on March 20, 2026, the fixture which had previously exceeded the AL was retested. During this resampling event, the fixture was below the AL and was returned to service.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, attached. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.