Testing Results

Rockwood Summit High
Updated

SCI collected 89 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Results Retest 2nd Draw Results 2nd Remediation Retest Result Returned to Service
Room 252 Sink 1 11.5 replaced aerator <1.0 <1.0     12/13/2023
Room 253 Sink 9.84 replaced aerator 10.3 2.3 fixture to be replaced <1.0  
Kitchen Handwash Sink 6.37 replaced aerator 2.8 <1.0     11/30/2023
Kitchen Right Faucet, Double Basin Sink 5.18 replaced aerator 4.2 <1.0     11/30/2023
Kitchen South Sink 8.43 replaced aerator 5.8 <1.0 fixture to be replaced 5.54  
Kitchen Left Wall Mounted Faucet 12.8 replaced aerator 15.2 <1.0 fixture to be replaced <1.0  
Kitchen Central Sink 15.2 replaced aerator 5.2 <1.0 fixture to be replaced <1.0  
Kitchen Left Faucet, Triple Basin Sink 7.91 replaced aerator <1.0 <1.0     11/30/2023
Kitchen Center Faucet, Triple Basin Sink 5.95 replaced aerator 1.4 <1.0     11/30/2023
Room 432 by Door 11 Right Drinking Fountain 29.4   21.6        
Room 432 by Door 11 Center Drinking Fountain 20.5   7.68        
Room 432 by Door 11 Left Drinking Fountain 7.1   1.74        