Testing Results
Rockwood Summit High
SCI collected 89 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.
| Sample Location | Sample Description | Result (ppb) | 1st Remediation | Retest 1st Draw Results | Retest 2nd Draw Results | 2nd Remediation | Retest Result | Returned to Service |
|---|---|---|---|---|---|---|---|---|
| Room 252 | Sink 1 | 11.5 | replaced aerator | <1.0 | <1.0 | 12/13/2023 | ||
| Room 253 | Sink | 9.84 | replaced aerator | 10.3 | 2.3 | fixture to be replaced | <1.0 | |
| Kitchen | Handwash Sink | 6.37 | replaced aerator | 2.8 | <1.0 | 11/30/2023 | ||
| Kitchen | Right Faucet, Double Basin Sink | 5.18 | replaced aerator | 4.2 | <1.0 | 11/30/2023 | ||
| Kitchen | South Sink | 8.43 | replaced aerator | 5.8 | <1.0 | fixture to be replaced | 5.54 | |
| Kitchen | Left Wall Mounted Faucet | 12.8 | replaced aerator | 15.2 | <1.0 | fixture to be replaced | <1.0 | |
| Kitchen | Central Sink | 15.2 | replaced aerator | 5.2 | <1.0 | fixture to be replaced | <1.0 | |
| Kitchen | Left Faucet, Triple Basin Sink | 7.91 | replaced aerator | <1.0 | <1.0 | 11/30/2023 | ||
| Kitchen | Center Faucet, Triple Basin Sink | 5.95 | replaced aerator | 1.4 | <1.0 | 11/30/2023 | ||
| Room 432 by Door 11 | Right Drinking Fountain | 29.4 | 21.6 | |||||
| Room 432 by Door 11 | Center Drinking Fountain | 20.5 | 7.68 | |||||
| Room 432 by Door 11 | Left Drinking Fountain | 7.1 | 1.74 |