SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 28, 2023, SCI initially collected 51 drinking water samples (RVMS-1 though RVMS-51) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 9 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. These fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on November 17 and 22, 2023, 6 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw samples were collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this sampling event 2 of the sampled fixtures were below the AL and were returned to service. The remaining fixture was above the AL, and further remediation activities were recommended.

During SCI’s resampling event on June 19, 2024, the remaining 7 fixtures which previously exceeded the AL were resampled. During this resampling event, all fixtures were below the AL and were returned to service.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures. Figures depicting the locations of the sampled water fixtures are enclosed.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, below. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

Sample Number Sample Location Sample Description Initial Result (ppb) Resampling - First Draw (ppb) Resampling - Second Draw (ppb) 2nd Resample (ppb)
RVMS-23 Kitchen North Handwash Sink 16.1 9.2 <1.0 2.14
RVMS-28 Kitchen Central Handwash Sink 6.77 2.1 <1.0 NS
RVMS-34 Hallway by Room 1905 Left Fountain 10.3 <1.0 NS
RVMS-35 Hallway by Room 1905 Left Bottle Filler 36.8 <1.0 NS
RVMS-36 Hallway by Room 1905 Right Fountain 19.3 <1.0 NS
RVMS-37 Hallway by Room 1905 Right Bottle Filler 53.5 <1.0 NS
RVMS-39 Room 1907 (FACS) Sink 2 (Central/South) 7.76 <1.0 <1.0 NS
RVMS-44 Hallway by Room 2004 Water Fountain 19.4 1.24 NS
RVMS-45 Hallway by Room 2004 Bottle Filler 89.4 <1.0 NS

NS – Not Sampled

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.