Testing Results

Selvidge Middle
Updated

SCI collected 44 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation 2nd Retest Result Returned to Service
Kitchen Right Faucet Triple Basin Sink 6.13 replaced aerator 1.9 <1.0     12/4/2023
Kitchen3.1 South Sink 7.23 replaced aerator 3.1 <1.0     12/4/2023
Kitchen North Sink 9.77 replaced aerator 1.6 <1.0     12/4/2023
Kitchen Kettle Faucet 7.54 replaced aerator 9.8 6.2 fixture to be replaced 2.52  
  Sink 5 38.0 replaced aerator <1.0 <1.0     12/11/2023