Testing Results

Stanton Elementary
Updated

SCI collected 24 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water sample that exceeded the AL is identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result Returned to Service
Kitchen Handwash Sink 11.3 replaced aerator 1.3 <1.0  

Download the Report (PDF)