Wildwood Middle
Updated

SCI collected 56 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result 2nd Remediation Retest Result Returned to Service
Kitchen Double Sink Left Faucet 6.59 replaced aerator <1.0 <1.0     1/18/2024
Kitchen Triple Basin Center Faucet 9.0 replaced aerator <1.0 <1.0     1/18/2024
Kitchen Triple Basin Right Faucet 6.44 replaced aerator <1.0 <1.0     1/18/2024
Kitchen Faucet on Side of Sink 68.7 replaced aerator 81.5 5.6      
Kitchen Left Wall Mounted Faucet 12.4 replaced aerator 11.6 27.5      
Kitchen Mixer Faucet 65.9 replaced aerator 11.7 2.7 replaced fixture    