SCI collected “first draw” samples which consisted of collecting a water sample from each fixture or sample location after it remained stagnant for at least eight hours. Prior to sampling, SCI first mobilized to the site to flush the identified potable water fixtures throughout the structure. Once each fixture was flushed, a sign was placed on the fixture indicating it should not be used. SCI then revisited the site, after a minimum of eight hours, to collect water samples from the fixtures.

On July 31, 2023, SCI initially collected 56 drinking water samples (WMS-1 through WMS-56) from various water fixtures located throughout the structure and submitted them for analytical testing. During this sampling event, 8 sample locations exceeded the action level (AL) of 5.0 micrograms lead per liter of water. These fixtures were taken out of service until remediation activities could be completed.

During SCI’s resampling event on December 14, 2023, 16 drinking water samples were collected from fixtures which exceeded 5.0 micrograms lead per liter of water. In addition to first draw samples, SCI also collected second draw samples during the resampling event. The second draw sample was collected after the first draw sample and consisted of flushing the fixture for approximately 30 seconds and then collecting the sample. The purpose of the second draw sample is to aid in pinpointing any potential lead contamination and determine appropriate remediation. During this sampling event 3 of the sampled fixtures were below the AL and were returned to service. Two of the fixtures were removed. The remaining 3 fixtures were above the AL, and further remediation activities were recommended.

During SCI’s resampling event on March 29, 2024, 1 fixture which previously exceeded the AL was resampled. During this resampling event, the fixture was still above the AL, and further remediation activities were recommended.

During SCI’s resampling event on July 7, 2025, 3 fixtures which previously exceeded the AL were resampled. During this resampling event, 1 fixture was below the AL and was returned to service. The other two fixtures were above the AL and were removed.

All drinking water samples were analyzed for total lead by U.S. EPA Method 200.8. SCI collected a minimum of 250 milliliters of water from each location. Sampled water was containerized in laboratory-provided sample containers and shipped to the accredited lab using standard chain-of-custody procedures.

The drinking water samples were analyzed for lead in accordance with the GTLOSDWA Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which initially exceeded the AL are identified in Table 1, below. Additionally, the results of SCI’s resampling efforts are included in the right-hand columns below. Results in bold from SCI’s resampling indicate a result greater than the AL. A copy of the analytical test results and chain-of-custody for all samples is enclosed.

Sample Number Sample Location Sample Description Initial Result (ppb) Resampling - First Draw (ppb) Resampling -  Second Draw (ppb) 2nd Resample (ppb) Third Resampling (ppb)
WMS-13 Kitchen Double Sink Left Faucet 6.59 <1.0 <1.0 NS
WMS-16 Kitchen Triple Basin Center Faucet 9.0 <1.0 <1.0 NS
WMS-17 Kitchen Triple Basin Right Faucet 6.44 <1.0 <1.0 NS
WMS-20 Kitchen Faucet on Side of Sink 68.7 81.5 5.6 3.07 NS
WMS-21 Kitchen Left Wall Mounted Faucet 12.4 11.6 27.5 16.4 NS (removed)
WMS-24 Kitchen Left Combi-Oven 47.9 13.8 17.9 NS (removed)
WMS-25 Kitchen Right Combi-Oven 5.20 7.0 <1.0 NS (removed)
WMS-26 Kitchen Mixer Faucet 6.59 11.7 2.7 24.5 12.2 [1]

NS –Not Sampled
[1] Fixture removed from service

As previously mentioned, no drinking water samples exceeded the AL of 5 ppb. Therefore, all tested fixtures are compliant per GTLOSDWA and should be tested every five years.