Skip To Main Content

Logo Image

Rockwood School District

Logo Title

Testing Results

Woerther Elementary
Updated

SCI collected 45 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The drinking water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act”, Section 160.077, which establishes an action level (AL) of 5 parts per billion (ppb). The drinking water samples which exceeded the AL are identified below.

Sample Location Sample Description Result (ppb) 1st Remediation Retest 1st Draw Result Retest 2nd Draw Result Returned to Service
Gym Bottle Filler 10.5   1.68    
Room 41 Water Fountain 5.63 removed     N/A

Download the Report (PDF)

All Results